Thursday 26 November 2026
Security

CISA warns of critical unpatched Danfoss controller flaw

The stack-based buffer overflow in AK-SM 8xxA controllers can be triggered without authentication and may allow remote code execution. Danfoss plans a fix in version 5.5.x but no patch is available.

Large Danfoss office building exterior in Nordborg, Denmark
Danfoss's main headquarters building in Nordborg, Denmark. Photograph: Schnatzel/Wikimedia Commons (public domain)

The U.S. Cybersecurity and Infrastructure Security Agency said in an ICS advisory that a stack-based buffer overflow in the Danfoss AK-SM 8xxA Series controller can be triggered without authentication. The flaw, CVE-2026-129713, is in an unauthenticated CGI handler and can be triggered by specially crafted HTTP or HTTPS POST requests. CISA said exploitation can cause memory corruption, restart the webserver, and potentially allow arbitrary code execution with webserver privileges.

CISA rated the vulnerability 9.8 under CVSS v3.1 and 9.3 under CVSS v4.0. Danfoss will address the issue in the upcoming 5.5.x software release, and future releases will no longer allow users to disable Strict Mode, according to the advisory. Until the update, Danfoss recommends keeping devices off the public internet, restricting remote access through a VPN or other protected network architecture, running controllers in Strict Mode, and using strong unique passwords. CISA said it has not received reports of public exploitation targeting CVE-2026-129713 at this time. Carlo Meijer of Midnight Blue reported the vulnerability to CISA.

BleepingComputer reported that Danfoss controllers have been compromised in recent attacks at food retail locations around Europe where attackers changed cooling settings from afar. The AK-SM 8xxA controllers act as hubs that manage cooling for supermarkets and convenience stores, handling hardware including display cases and compressor racks, logging temperatures, and sending alerts. Depending on the model, which includes the 820A, 850A, and 880A, some can also manage store lighting and HVAC.

BleepingComputer said Danfoss issued security advisory DSA-2026-12-01 on November 20, confirming the flaw will be patched in version 5.5.x and that the update will no longer allow disabling Strict Mode. No patch is available yet.

BleepingComputer also recounted earlier incidents. On October 11 and 12, attacks blamed on Iran's Shahid Kaveh unit, which is tied to the IRGC, hit refrigeration controllers made by Danfoss and Copeland/Dixell in French supermarkets and food retailers, changing defrost settings. On November 2, attackers remotely shut down refrigeration equipment or altered settings at 115 or more store locations in Ireland, Estonia, Luxembourg, Romania, Sweden, Belgium and the Netherlands. Supplier Sabcobel stated that the intruders exploited the same security hole as in the French incidents from October, which again pointed to Danfoss equipment. That day, intruders believed to be tied to the earlier operation hit a refrigeration vendor serving France's national blood service and altered cold-storage settings at three facilities.

CISA's guidance for operators is to minimize network exposure for control system devices, place control system networks behind firewalls and separate from business networks, and use VPNs that have been updated to the current version when remote access is required.

Sources: Cybersecurity and Infrastructure Security Agency CISA, BleepingComputer

Noor Haddad

Noor Haddad covers attacks, breach disclosures and exploited vulnerabilities for Five Nines. Noor writes from CISA and vendor advisories, SEC disclosures and published reporting.

Corrections. Report an error to corrections@thefivenines.com. We list substantive corrections on the corrections page.